Filtered by vendor Schneider-electric Subscriptions
Total 784 CVE
CVE Vendors Products Updated CVSS v3.1
CVE-2017-6028 1 Schneider-electric 4 Modicon M241, Modicon M241 Firmware, Modicon M251 and 1 more 2025-04-20 9.8 Critical
An Insufficiently Protected Credentials issue was discovered in Schneider Electric Modicon PLCs Modicon M241, all firmware versions, and Modicon M251, all firmware versions. Log-in credentials are sent over the network with Base64 encoding leaving them susceptible to sniffing. Sniffed credentials could then be used to log into the web application.
CVE-2017-5155 1 Schneider-electric 1 Wonderware Historian 2025-04-20 N/A
An issue was discovered in Schneider Electric Wonderware Historian 2014 R2 SP1 P01 and earlier. Wonderware Historian creates logins with default passwords, which can allow a malicious entity to compromise Historian databases. In some installation scenarios, resources beyond those created by Wonderware Historian may be compromised as well.
CVE-2017-9961 1 Schneider-electric 1 Pro-face Gp Pro Ex 2025-04-20 N/A
A vulnerability exists in Schneider Electric's Pro-Face GP Pro EX version 4.07.000 that allows an attacker to execute arbitrary code. Malicious code installation requires an access to the computer. By placing a specific DLL/OCX file, an attacker is able to force the process to load arbitrary DLL and execute arbitrary code in the context of the process.
CVE-2017-9627 1 Schneider-electric 1 Wonderware Archestra Logger 2025-04-20 8.6 High
An Uncontrolled Resource Consumption issue was discovered in Schneider Electric Wonderware ArchestrA Logger, versions 2017.426.2307.1 and prior. The uncontrolled resource consumption vulnerability could allow an attacker to exhaust the memory resources of the machine, causing a denial of service.
CVE-2017-13997 1 Schneider-electric 2 Wonderware Indusoft Web Studio, Wonderware Intouch 2025-04-20 N/A
A Missing Authentication for Critical Function issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 or prior, and InTouch Machine Edition v8.0 SP2 or prior. InduSoft Web Studio provides the capability for an HMI client to trigger script execution on the server for the purposes of performing customized calculations or actions. A remote malicious entity could bypass the server authentication and trigger the execution of an arbitrary command. The command is executed under high privileges and could lead to a complete compromise of the server.
CVE-2017-9960 1 Schneider-electric 1 U.motion Builder 2025-04-20 N/A
An information disclosure vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which the system response to error provides more information than should be available to an unauthenticated user.
CVE-2016-8367 1 Schneider-electric 16 Magelis Gto Advanced Optimum Panel, Magelis Gto Advanced Optimum Panel Firmware, Magelis Gtu Universal Panel and 13 more 2025-04-20 5.3 Medium
An issue was discovered in Schneider Electric Magelis HMI Magelis GTO Advanced Optimum Panels, all versions, Magelis GTU Universal Panel, all versions, Magelis STO5xx and STU Small panels, all versions, Magelis XBT GH Advanced Hand-held Panels, all versions, Magelis XBT GK Advanced Touchscreen Panels with Keyboard, all versions, Magelis XBT GT Advanced Touchscreen Panels, all versions, and Magelis XBT GTW Advanced Open Touchscreen Panels (Windows XPe). An attacker can open multiple connections to a targeted web server and keep connections open preventing new connections from being made, rendering the web server unavailable during an attack.
CVE-2017-7689 1 Schneider-electric 2 Homelynk Controller Lss100100, Homelynk Controller Lss100100 Firmware 2025-04-20 9.8 Critical
A Command Injection vulnerability in Schneider Electric homeLYnk Controller exists in all versions before 1.5.0.
CVE-2017-5157 2 Schneider-electric, Schneider Electric 2 Homelynk Controller Lss100100, Homelynk Controller Lss100100 Firmware 2025-04-20 N/A
An issue was discovered in Schneider Electric homeLYnk Controller, LSS100100, all versions prior to V1.5.0. The homeLYnk controller is susceptible to a cross-site scripting attack. User inputs can be manipulated to cause execution of JavaScript code.
CVE-2017-9631 1 Schneider-electric 1 Wonderware Archestra Logger 2025-04-20 7.5 High
A Null Pointer Dereference issue was discovered in Schneider Electric Wonderware ArchestrA Logger, versions 2017.426.2307.1 and prior. The null pointer dereference vulnerability could allow an attacker to crash the logger process, causing a denial of service for logging and log-viewing (applications that use the Wonderware ArchestrA Logger continue to run when the Wonderware ArchestrA Logger service is unavailable).
CVE-2017-7965 1 Schneider-electric 1 Somachine Hvac 2025-04-20 7.3 High
A buffer overflow vulnerability exists in Programming Software executable AlTracePrint.exe, in Schneider Electric's SoMachine HVAC v2.1.0 for Modicon M171/M172 Controller.
CVE-2016-5818 1 Schneider-electric 2 Powerlogic Pm8ecc, Powerlogic Pm8ecc Firmware 2025-04-20 N/A
An issue was discovered in Schneider Electric PowerLogic PM8ECC device 2.651 and older. Undocumented hard-coded credentials allow access to the device.
CVE-2017-6019 1 Schneider-electric 2 Conext Combox 865-1058, Conext Combox 865-1058 Firmware 2025-04-20 N/A
An issue was discovered in Schneider Electric Conext ComBox, model 865-1058, all firmware versions prior to V3.03 BN 830. A series of rapid requests to the device may cause it to reboot.
CVE-2016-8374 1 Schneider-electric 16 Magelis Gto Advanced Optimum Panel, Magelis Gto Advanced Optimum Panel Firmware, Magelis Gtu Universal Panel and 13 more 2025-04-20 7.5 High
An issue was discovered in Schneider Electric Magelis HMI Magelis GTO Advanced Optimum Panels, all versions, Magelis GTU Universal Panel, all versions, Magelis STO5xx and STU Small panels, all versions, Magelis XBT GH Advanced Hand-held Panels, all versions, Magelis XBT GK Advanced Touchscreen Panels with Keyboard, all versions, Magelis XBT GT Advanced Touchscreen Panels, all versions, and Magelis XBT GTW Advanced Open Touchscreen Panels (Windows XPe). An attacker may be able to disrupt a targeted web server, resulting in a denial of service because of UNCONTROLLED RESOURCE CONSUMPTION.
CVE-2020-25178 3 Rockwellautomation, Schneider-electric, Xylem 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more 2025-04-16 7.5 High
ISaGRAF Workbench communicates with Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x using TCP/IP. This communication protocol provides various file system operations, as well as the uploading of applications. Data is transferred over this protocol unencrypted, which could allow a remote unauthenticated attacker to upload, read, and delete files.
CVE-2020-25182 3 Rockwellautomation, Schneider-electric, Xylem 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more 2025-04-16 6.7 Medium
Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x searches for and loads DLLs as dynamic libraries. Uncontrolled loading of dynamic libraries could allow a local, unauthenticated attacker to execute arbitrary code. This vulnerability only affects ISaGRAF Runtime when running on Microsoft Windows systems.
CVE-2020-25176 3 Rockwellautomation, Schneider-electric, Xylem 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more 2025-04-16 9.1 Critical
Some commands used by the Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x eXchange Layer (IXL) protocol perform various file operations in the file system. Since the parameter pointing to the file name is not checked for reserved characters, it is possible for a remote, unauthenticated attacker to traverse an application’s directory, which could lead to remote code execution.
CVE-2020-25184 3 Rockwellautomation, Schneider-electric, Xylem 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more 2025-04-16 7.8 High
Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x stores the password in plaintext in a file that is in the same directory as the executable file. ISaGRAF Runtime reads the file and saves the data in a variable without any additional modification. A local, unauthenticated attacker could compromise the user passwords, resulting in information disclosure.
CVE-2020-25180 3 Rockwellautomation, Schneider-electric, Xylem 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more 2025-04-16 5.3 Medium
Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x includes the functionality of setting a password that is required to execute privileged commands. The password value passed to ISaGRAF Runtime is the result of encryption performed with a fixed key value using the tiny encryption algorithm (TEA) on an entered or saved password. A remote, unauthenticated attacker could pass their own encrypted password to the ISaGRAF 5 Runtime, which may result in information disclosure on the device.
CVE-2016-4529 1 Schneider-electric 3 M171, M172, Somachine Hvac Firmware 2025-04-12 7.3 High
An unspecified ActiveX control in Schneider Electric SoMachine HVAC Programming Software for M171/M172 Controllers before 2.1.0 allows remote attackers to execute arbitrary code via unknown vectors, related to the INTERFACESAFE_FOR_UNTRUSTED_CALLER (aka safe for scripting) flag.